Watts 994 Manual de usuario

Busca en linea o descarga Manual de usuario para Accesorios para el agua Watts 994. Watts 994 User Manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 8
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
RP/IS-994/994RPDA
NOTICE
Inquire with governing authorities for local installation requirements
NOTICE
For Australia and New Zealand: Pipeline strainers should be installed
between the upstream shutoff valve and the inlet of the backflow
preventer.
994
Installation, Maintenance, & Repair
Series 994/994RPDA
Reduced Pressure Zone Assemblies
Reduced Pressure Detector Assemblies
Sizes: 2
1
2" – 10" (65 – 250mm)
Local building or plumbing codes may require modifications to the
information provided. You are required to consult the local building and
plumbing codes prior to installation. If this information is not consistent
with local building or plumbing codes, the local codes should be fol-
lowed.
Need for Periodic Inspection/Maintenance: This product must be
tested periodically in compliance with local codes, but at least once per
year or more as service conditions warrant. Corrosive water conditions,
and/or unauthorized adjustments or repair could render the product
ineffective for the service intended. Regular checking and cleaning of the
product’s internal components helps assure maximum life and proper
product function.
WARNING
!
Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information
can result in death, serious personal injury, property
damage, or damage to the equipment.
Keep this Manual for future reference.
Testing
For field testing procedure, refer to Watts installation sheets
IS-TK-DP/DL, IS-TK-9A, IS-TK-99E and IS-TK-99D found on
www.watts.com.
For troubleshooting guide, refer to literature S-TSG.
For other repair kits and service parts, refer to our Backflow Preven-
tion Products Repair Kits & Service Parts price list PL-RP-BPD
found on www.watts.com.
For technical assistance, contact your local Watts representative.
Vista de pagina 0
1 2 3 4 5 6 7 8

Indice de contenidos

Pagina 1 - Series 994/994RPDA

RP/IS-994/994RPDANOTICEInquire with governing authorities for local installation requirements NOTICEFor Australia and New Zealand: Pipeline strainers

Pagina 2 - 2 65 55 gpm 2

2Location and Installation Considerations1. Backflow preventers must be installed in high-visibility lo ca tions in order to allow for immediate noti

Pagina 3 - Above Ground

3Series 994 Installation Instructions*For additional information on Watts insulated enclosures refer to literature ES-WB.ParallelIndoorsAbove Ground12

Pagina 4

4Servicing First and Second ChecksSeries 994/994RPDA 4" and 6" (100 – 150mm)Removing Check Assemblies (Before servicing be sure shutoff valv

Pagina 5 - First Check

5Servicing First and Second ChecksSeries 994/994RPDA 8" and 10" (200 – 250mm)1. Slowly open all ball valves to relieve air and water press

Pagina 6 - Servicing the Relief Valve

6Servicing the Relief Valve 1. The relief valve may be serviced while on or off the backflow preventer valve. 2. NOTICE DO NOT USE A PIPE WRENCH

Pagina 7 - Test No. 1 - Relief Valve

7Testing - Reduced Pressure Zone AssembliesWatts TK-DLThe following Test Procedure is one of several that is recognized throughout the United States f

Pagina 8 - Troubleshooting Guide

Problem Cause SolutionA. Assembly discharges from differential relief valve during no flow condition.Fouled first check Disassemble and clean No. 1 c

Modelos relacionados 994RPDA

Comentarios a estos manuales

Sin comentarios